4) Network insulation displacement connectors shall be provided with all stations.
PART 3 EXECUTION
3.1 INSTALLATION
A. Install all items in conformity with standard trade practices and Manufacturer’s recommendations
B. Consult and coordinate work with trades doing adjoining work.
C. Position all items accurately as indicated in the Drawings and true to plumb line and level.
Maintain maximum headroom and clearance at all points.
D. Do not uncrate, unpack, unwrap or install control console, video monitor(s), remote controls or
other auxiliary control components until construction is complete and environment is clean and
dust-free.
E. Dealer is responsible for all components required to install and complete an operating system.
(1) The Theatrical Dealer is responsible for the complete installation of the specified
equipment. The installation shall be done by a licensed and bonded electrical
contractor with over ten (10) years of experience installing theatrical systems and
experienced in working with theatrical dealers. The electrical contractor shall be sub to
the Theatrical Dealer and shall be responsible for both high and low voltage
installation.
3.2 WIRING
A. Power Wiring
1. Install wiring as specified in Division 16 for hard wired connections. Install wiring in
raceways except cable and plug connections.
2. Install power wiring with a separate neutral for each output circuit from main dimmer and
for each house and stage lighting circuit.
3. Install power and control wiring for the stage lighting system in raceways that are unique
to only that system.
B. Signaling, Remote-Control and Power-Limited Circuits
1. Size conductors according to lighting control device manufacturer’s written instructions,
unless otherwise indicated.
2. Remote-control circuits associated with emergency lighting control shall be installed
complying with Class 1 Circuit standards.
3. Install data-transmission cabling per manufacturer’s recommendations
C. Wiring within enclosures: bundle, lace and train conductors to terminal points
D. Splices, Taps and Terminations: Make connections only on numbered terminal strips in junction,
pull and outlet boxes; terminal cabinets; and equipment enclosures.
E. Remove wall plates and protect devices and assemblies during painting.
F. Support lighting fixtures, distribution components and accessories per manufacturer’s
recommendation. Equip all pipe-mounted equipment with safety cables that are secured to
supporting pipe.
G. Ground equipment according to Division 16 Section.
3.3 IDENTIFICATION
A. Identify components, power and control wiring according to Division 16 Section.