2
9
2) It shall be possible to view and modify connectivity settings
3) It shall be possible to view status information
4) It shall be possible to view and modify LCD screen settings
5) It shall be possible to perform Touchscreen calibration
6) It shall be possible to view and modify audio settings
7) The appearance of the setup display shall be standard and not editable
8) The setup display may be invoked from within the user-defined configuration
and/or physical button on the Portable Touchscreen
9) There shall be a default protected method to invoke the setup display
c) Configurations
1) It shall be possible to have multiple configurations stored within an LCD
Station
2) The Portable Touchscreen shall automatically load the required configuration
based on connection point to the system
3) Only one configuration may be active on the LCD Station
4) It shall be possible for Portable Touchscreen Stations connected via the
Echelon® Link power network to select a configuration automatically based on
the configuration of the physical connection.
5) Where multiple configurations are stored there shall be a setup menu to allow
selection of a configuration
6) Each configuration shall be identified as a different Station within the System
d) Operation
1) The Unison Paradigm Control System shall be designed to allow control of
lighting and associated systems via Touchscreen controls. System shall allow
the control of presets, sequences, macros and time clock events.
A) System presets shall be programmable via Button,
Button/Fader or Touchscreen stations, or LightDesigner
software.
B) Presets shall have a discrete fade time, programmable
from zero to 84,600 seconds with a resolution of one
hundred milliseconds.
C) Presets shall be selectable via Touchscreen stations.
2) System macros and sequences shall be programmable via LightDesigner
system software.
A) Macro and sequence steps shall provide user selectable
steps, and allow the application of conditional logic.
B) Macro and sequences shall be activated by button, time
clock event or LightDesigner software.
3) System time clock events shall be programmable via the Touchscreen,
LightDesigner system software, the processor user interface, or the internal
web server.